For a cyclic refrigerator or heat pump, the First Law gives Q_H = Q_C + W_in. The refrigerator COP is COP_R = Q_C/W_in, while the heat-pump COP is COP_HP = Q_H/W_in. Substituting the energy balance into the heat-pump definition gives COP_HP = (Q_C + W_in)/W_in = COP_R + 1. This relationship holds when both COP values refer to the same operating cycle and the same heat and work transfers. The refrigerator COP measures cooling delivered per unit of work; the heat-pump COP measures heating delivered per unit of work. Because the heating output includes both the heat extracted from the cold source and the work input, the heat-pump COP is exactly one greater than the refrigerator COP for the same cycle. Both COP values can exceed one without violating energy conservation.
Relationship Between Refrigerator and Heat-Pump Performance
A refrigerator and a heat pump can be the same physical device viewed from different objectives. Their coefficients of performance are related through the energy balance between heat absorbed, heat rejected, and work supplied.
COP_HP = COP_R + 1
Explanation
Variables
| Symbol | Meaning | Unit |
|---|---|---|
COP_HP | Heating coefficient of performance | Dimensionless |
COP_R | Refrigeration coefficient of performance | Dimensionless |
Q_H | Heat delivered to the hot region | J |
Q_C | Heat removed from the cold region | J |
W_in | Work input | J |
Example or application
If a device has a refrigerator COP of 3.5 in a particular operating mode, its heat-pump COP for the same cycle is 4.5, because COP_HP = COP_R + 1.
Sources and verification
Sources are shown as provided in the project data. Not every source has yet been independently verified. Please report errors or missing citations.
- Çengel, Boles and Kanoglu, Thermodynamics: An Engineering Approach; Moran et al., Fundamentals of Engineering Thermodynamics.